Click&Go User’s Manual Examples and Applications
4-10
6. Select DI as the type to export the signal from the input module. In the 1. Dest. IP: field, enter
192.168.127.3 and click OK to save this setting.
7. Click OK to close the Logic Configuration window.
8. Click Download on the Rule-set Management Bar.
9. Select Yes when asked to restart and wait until the server has restarted and is back on-line.
10. Log in on the Server Settings tab, then go to the Click&Go Logic tab.
11. Click Run on the Rule-set Management Bar. The RDY LED will be flashing green, showing
that the ioLogik is now operating as an Active Ethernet I/O server, using the rule-set that was
just defined.
Output Module (192.168.127.3)
Rule 0: DI-0 at 192.168.127.154 mapped to DO-0
Rule 1: DI-1 at 192.168.127.154 mapped to DO-1
1. In ioAdmin, make sure that you have searched for and selected the correct ioLogik E2242 server,
at IP address 192.168.127.3. Also, make sure you are logged in on the Server Settings tab. Go
to the Click&Go Logic tab.
2. Double click #0 in the Rule-set. The Logic Configuration window will appear.
3. Make sure that Enable in the upper left hand corner is checked.
4. Select Enable peer-to-peer I/O.
5. Select Output channel, then select DO-0 for the first field, enter 192.168.127.154 for the
second field, and select DI-0 for the third field.
6. Click OK to close the Logic Configuration window.
7. Double click #1 in the Rule-set. The Logic Configuration window will appear.
8. Make sure that Enable in the upper left hand corner is checked.