Click&Go User’s Manual Click&Go V2 Developing Process
3-44
NOTE
Only DI channels that are set to DI mode can mirror remote DO channels. Event Counter
channels cannot be used for peer-to-peer I/O operation. For analog input and output channels,
they must be configured to the same voltage or current mode. Also, a digital channel can not
mirror an analog output channel or vise versa.
Configuring Output Module
The peer-to-peer I/O output module is configured using one Click&Go rule for each DO channel
that is mirroring a remote input channel. In the Click&Go tab, start a new rule, select Enable
peer-to-peer I/O, and then select Output channel. Specify the output channel that will mirror the
remote input channel, the IP address of the input module, and the input channel on the input module
whose signals will be mirrored. The input module must have specified the output module’s IP
address as a destination IP.
When properly configured, the specified output channel will mirror the signals received by the
specified remote input channel, as if the channels were physically connected. For example, If the
remote DI channel’s status changes to “ON”, the specified DO channel’s status will change to “ON”.
If the remote DI channel’s status changes to “OFF”, the DO channel’s status will change to “OFF”.
Once both the input and output modules have been configured start peer-to-peer I/O operation by
activating the rule-set on both units and providing a valid network connection to each unit.
NOTE
Only DO channels that are set to DO mode can mirror remote DI channels. Pulse Output
channels cannot be used for peer-to-peer I/O operation. For analog input and output channels,
they must be configured to the same voltage or current mode. Also, a digital channel can not
mirror an analog output channel or vise versa.