Click&Go User’s Manual Click&Go V2 Developing Process
3-30
THEN/ELSE actions can be specified as follows:
THEN/ELSE Actions Operators Remark
Counter RESET
Counter-x represents the number of the
Event Counter channel
DO ON, OFF
DO-x represents the number of the
channel.
Pulse Output STOP, START
Pulse Output-x represents the number of
the channel
AO
AO-x represents the number of the
channel.
Max Value: Depends on the analog
Modes or the result of scaling
Relay RESET
ResetCNT-x represents the number of
the relay channel.
Internal Register
Reg-x represents the number of the
internal register.
x = 00 to 23 / Trigger Value: 0 to 255
Remote Action
Action ID: 01 to 24
Number of Remote IP Addresses: 5 sets
Timer STOP, START, RESTART
Timer-x, x = 00 to 23
Max value: 4,294,967,295 seconds
SNMP Trap
I/O Status Bindings: 3 sets
Active Message ID / Source IP Unicode supported
e-Mail Create the contents of the e-Mail
CGI Command ID / Source IP
Specify the target URL and CGI
commands