Click&Go User’s Manual Click&Go V2 Developing Process
3-6
Analog Output Mode Selection
The only model that currently provides analog output channels is ioLogik E2240, which provides
both voltage and current output.
Mode Available
Number of Analog
Output Channels
Mode Selection:
Voltage
Mode Selection:
Current
ioLogik E2240 2 0 to 10 V 4 to 20 mA
When logged in as an administrator, double click on a channel in the I/O Configuration tab to
configure that channel’s settings. A window will open with configuration options for that channel.
Each AO channel will be configured to output either voltage or current according to the Range
Settings.
Temperature Input Mode Selection
Thermocouple (TC) and resistance temperature detector (RTD) sensors are mostly used to perform
temperature measurements. For Moxa ioLogik Active Ethernet I/O servers, selecting the
temperature input modes is equal to selecting the sensor types.
Mode Available
Number of
Temperature Input
Channels
Sensor Type Selection:
ioLogik E2260 6 RTD
Pt100, Pt200, Pt500, Pt1000, JPt100, JPt200, JPt500,
JPt1000, Ni 100, Ni 200, Ni 500, Ni 1000, Ni 120,
Resistance (1-310 mΩ), Resistance (1-620 mΩ),
Resistance (1-1250 mΩ), Resistance (1-2200 mΩ)
ioLogik E2262 8 TC
J, K, T, E, R, S, B, N Type and
78.126/39.062/19.532mV