Click&Go User’s Manual Click&Go V2 Developing Process
3-10
Internal Register Settings
Internal Register is a flag that can be used with the Click&Go logic internally or externally. The
24 sets of the internal registers can be polled and controlled by a SCADA software using standard
Modbus/TCP format, or be implemented to redirect the result of one Click&Go logic to another.
Default value of an internal register is “0”.
Register Number Initial Value
Internal Register Reg-0 to Reg-23 *0 to 255
Timer Settings
The Timer function allows users to delay an action, to trigger an action to run, or repeat an action.
A timer is activated by a change of the logic event. After the timed interval has expired, the output
will be performed.
There are 24 timers that can be implemented in the Click&Go V2 logic, and the default value of
their interval is set to “5 seconds” at the “STOP” state. Configure the interval before using them.
If default state is set to “START”, timer will start when the Click&Go logic is activated.
Timer Number Initial State Configuration
Timer Timer-0 to Timer-23 START, *STOP