Click&Go User’s Manual Click&Go V2 Developing Process
3-26
Host Connection Fail
The Host Connection Fail function refers to when an ioLogik detects the timeout from a remote
Modbus/TCP host and directs it to one of the IF condition of the Click&Go logic. Timeout can be
used to trigger an action such as resetting the attached power line on a DO or relay channel to
reboot the device. Select the IF condition to Host Connection Fail and click on the property button
(
) to enter the setting window.
More Info on Repeat Interval vs. Edge Detection
Combining the Timer function with other IF conditions allows actions to be repeated when the
specified logic is sustained. However, if a condition is based on edge detection (i.e., ON to OFF or
OFF to ON), it can only be triggered once.
The following scenarios illustrate how edge detection affects the Timer = N sec. In each diagram,
the statuses of three sensors are shown over a period of time, with a high signal corresponding to a
“true” condition. The green shaded area shows the duration of time that the IF conditions have been
met.