Click&Go User’s Manual Click&Go V2 Developing Process
3-16
IF Conditions
IF conditions are events that trigger the THEN/ELSE actions. Under the IF column, you can set
up to 3 conditions that must be satisfied for the actions under the THEN/ELSE column to take place.
As soon as the IF conditions are satisfied, the specified THEN/ELSE action is performed. For
example, an alarm can be activated when a door is opened. Use the pull downs to specify the
conditions and units of measurement (e.g. DI-0=OFF).
IF conditions can be specified as follows:
IF Conditions Operators Remark
DI
ON, OFF, ON to OFF,
OFF to ON, Change
DI-x represents the number of the
channel.
Counter =, >, <, >=, <=, Change
Counter-x represents the number of the
channel.
Max Counter Value: 4,294,967,295
AI =, >, <, >=, <=
AI-x represents the number of the
channel.
Max Value: Depends on the analog
Modes or the result of scaling
RTD =, >, <, >=, <=
RTD-x represents the number of the
channel.
Max Value: Depends on the mode
selection of RTD sensor
TC =, >, <, >=, <=
TC-x represents the number of the
channel.
Max Value: Depends on the mode
selection of TC sensor
Relay =, >, <, >=, <=
CurRelayCNT-x represents the current
relay counts of the channel.
Max Value: 4,294,967,295
Internal Register =
Reg-x represents the number of the
internal register.
x = 00 to 23 / Trigger Value: 0 to 255
Remote Action
Received Action ID: 01 to 24
Source IP Range:
0.0.0.1 to 223.255.255.254
Timer TIMEOUT
Timer-x, x = 00 to 23
Max value: 4,294,967,295 seconds