Click&Go User’s Manual Getting Started
2-7
Firmware Update
Firmware upgrade will be necessary to have the latest function support on the ioLogik products
(see Chap. 1). To do so, the Firmware Update tab is available after you log in ioAdmin utility as an
administrator. In the Firmware Upgrade tab, enter the path to the firmware file or click on the icon to
browse for the file. Click Update to update the ioLogik firmware. The wizard will lead you through
the process until the ioLogik is restarted.
Firmware upgrade with a jump version for specific ioLogik models may be required.
Model
Start
Version
Jump
Version
Final
Version
ioLogik E2210 V1.x V2.0 V3.x
ioLogik E2212 V1.0 V1.1 V3.x
ioLogik E2240 V1.x V2.2 V3.x
ioLogik E2214, E2242,
ioLogik E2260, E2262
V1.x N/A V3.x
For ioLogik E2210, E2212 and E2240, it is recommended to upgrade the jump version first, and
then upgrade again to the final version that supports Click&Go V2. For the rest of the models,
firmware upgrade can be performed directly to the latest version.
ATTENTION
Do not interrupt the firmware update process! An interruption in the process might result in
your device becoming unrecoverable.
After the firmware is updated, the ioLogik will restart and you will have to log in again to access
administrator functions.
The firmware on any attached I/O expansion module, such as an ioLogik R2000 server, must be
updated over the RS-485 bus. Firmware on cascaded modules cannot be updated over Ethernet.