ioLogik Cellular Micro RTU Controller Click&Go Logic
4-10
Defining Global Variables
Global Variables include Internal Register Settings, Timer Settings, SNMP Trap Server, E-Mail Server,
Active Message Server and SMS Phone Book. If these functions will be used in a Click&Go V2 rule-set, the
default configuration must first be set from the Global Variable Menu Bar.
The following global variables are only supported by ioLogik W5300 micro RTU controllers: SMS Phone Book,
Working/Off Working Day, FTP, Data Logging Profile List, and Internal Register(Float).
Internal Register (Integer) Settings
Internal Register (Integer) is a flag that can be used with the Click&Go logic internally or externally. The 24
sets of internal registers can be polled and controlled by SCADA software using standard Modbus/TCP format,
or implemented to redirect the result of one Click&Go logic to another.
The default value of an internal register is “0”.
Register Number Initial Value
Internal Register Reg-0 to Reg-23 *0 to 255
Timer Settings
The Timer function allows users to delay an action, trigger an action to run, or repeat an action. A timer is
activated by a change of the logic event. After the timed interval has expired, the output will be performed.
The 24 timers that can be implemented with Click&Go V2 logic have the default time interval set to 5 seconds
in the STOPstate. Be sure to configure the interval before using a timer.
With the default state set to START” the timer will start when the Click&Go logic is activated.