ioLogik Cellular Micro RTU Controller Planning and Assistance
Step 5: If the SMS alarm is triggered, an alarm message will be received with the reply notice.
Step 6: Follow this example’s settings. If the 1st receiver does not acknowledge with an SMS reply within 15
minutes, the ioLogik will send an alarm to the 2nd receiver. This loop will be repeated a total of 3 times.
For more SMS commands please refer to Appendix C
using the SMS related function, be sure to get an appropriate data plan from your cellular provider
. For
example, a SIM card
that only supports data service has the lowest priority to send or receive an
s, users must activate the voice service on this SIM to ensure faster response for the SMS.
strongly recommend checking with your service provider for details.
The function is dependent on the firmware version. Be sure to use firmware version V1.3 or above for the
ioLogik W5312 series, V1.5 or above for the ioLogik W5340 series, and V1.2 or
above for the ioLogik
-HSDPA series.