ioLogik Cellular Micro RTU Controller Utility: ioAdmin
3-39
PING Check before system restart: A remote destination is used in this setting to indicate if the Internet
connection is still alive. The user can specify a public IP or URL and the number of retries that are allowed.
Dest IP/URL: Can either be an AOPC server IP or any public URL for the device to check its connection with
the internet.
Auto Retry: Will be activated when the AOPC can’t connect with the AOPC server. The W5300 will tell the
machine to ping the Dest IP/URL to check for an Internet connection.
Continuous Check Until 3 failures: The W5300 continuously check its connection with the IP/URL to
ensure that it is constantly connected to the internet (could incur a high cose, depending on your cellular
plan).
Network Log: The Network Log records the activity of the cellular connections. Click the Export Log
button to retrieve the log file.
NOTE
Since there is a limit to the number of times you can write to system memory, we strongly recommend
installing a
t least a 1 GB SD that the ioLogik W5300 can use for logging.
Meter/Sensor
OP Mode
The ioLogik W5300 supports four OP modes, Transparent Serial Tunnel (TCP Server and TCP Client),
Modbus TCP <-> Modbus RTU Gateway, and Modbus Serial Tags.
Transparent Serial Tunnel: Transparent Serial Tunnel mode creates a TCP socket to a remote host
program and transparently sends and receives data to attached legacy serial devices.
Modbus RTU Gateway: This function allows users to attach a serial Modbus/RTU meter to the ioLogik
W5300’s serial port; in this case, the ioLogik W5300 will act as a Modbus/RTU to Modbus/TCP gateway.
Modbus Serial Tags: This function allows users to attach a serial Modbus/RTU meter to the ioLogik W5300’s serial port
and create the serial tags in the Active OPC Server so that a SCADA system can access this serial data directly via OPC
connections. In this case, the Modbus/RTU serial devices will appear to be embedded in the ioLogik W5300 micro RTU
Controller.