ioLogik Cellular Micro RTU Controller Planning and Assistance
5-21
Updating Serial Tags to SCADA System with
Active OPC Server over a Cellular Network
Scenario: For many applications, a remote site not only needs to be monitored for physical IOs that measure
environmental or facility conditions, but must also coordinate data output from serial meters. The ioLogik
W5300 has a 3-in-1 serial port built in that supports attaching field serial Modbus/RTU meters (either RS-232
or RS-485), and allows the integration of this serial data so that it can be uploaded to the SCADA system via the
Moxa Active OPC Server software.
Setup Procedure
Step 1: Start ioAdmin as administrator.
Step 2: Choose the Meter/Sensor tab.
Step 3: Set the serial port parameters: RS-232, RS-485, Baudrate, Stop Bits, etc.
Step 4: Click Modbus Serial Tags to choose the operation mode.
Step 6: Click on the Tag Settings button at the right.
Step 7: Add the serial Tags. Refer to the attached serial device’s Modbus Address table for further details.