ioLogik Cellular Micro RTU Controller Planning and Assistance
5-12
Setup Procedure:
Step 1: Open ioAdmin and set up your micro controller as follows:
Connect DO-4 to DI-0.
1.2. Configure DO-4 for 1 Hz pulse output.
1.3. Configure DI-0 for counter input mode.
Step 2: We assume that DI-0 is already connected to the flow meter.
Step 3: Right click on DI-0 from the I/O Configuration panel.
Step 4: Select the Counter Scaling tab in the popup window.
Step 5: Configure the scaling formula and update the sampling time.
Step 6: Close the popup window.
Step 7: Choose virtual channel (shown as VC-00), and select the source channel. We use DI-00 for this
example.
Step 8: Select the operation mode from Max, Min., Average, Accumulation, Instantaneous, and Incremental.
Step 9: Close the popup window.
Step 10: Check the value on the I/O configuration Panel. The virtual channel value can be updated to AOPC
with the Active Tags function.