ioLogik Cellular Micro RTU Controller Planning and Assistance
5-5
In the following sections, we illustrate how to set up an environment for the ioLogik W5300.
Using ioAdmin to Perform Simple Data
Monitoring from a Remote Site
Scenario: Users would like to check the I/O status at the central site. The ioAdmin monitoring and
configuration utility will be used to monitor the remote site I/O status. The related network structure and
diagram are shown below.
Environment:
1. Active OPC server: Public Static IP: 59.124.42.169
Internal Static IP: 192.168.19.19
2. Central site: Internal Static IP: 192.168.19.207
Diagram:
Implementation:
Step 1: Following Chapter 2 instructions, insert the SIM card in the W5340 and connect it to the sensors.
Step 2: Install ioAdmin in the host and run ioAdmin.
Step 3: Connect to the host and ioLogik W5340 via the Ethernet Console.
Step 4: Configure the “Cellular settings,” including the Dial-up setting and Operation Modes.
Step 5: Input the Active OPC Server address on the “Active Tagspanel.
Step 6: Install the Active OPC Server on a PC with static IP address and ensure the IP address of the Active OPC
Server is available and accessible from the remote ioLogik.
Step 7: Before starting use Active OPC server, make sure TCP ports 9900, 9500, 9300, and 502 are available
by configuring the local router or firewall in the IP address is located in the LAN.