ioLogik Cellular Micro RTU Controller Utility: ioAdmin
3-24
ATTENTION
The expansion module should be installed on the same network segment or the ioLogik W5300 will not be able
to detect it. This is the only limitation. You do not need to connect them directly, and they can also be
co
nnected through the network switch.
The sequence is indicated in the Slot# column.
To activate the function, restart the ioLogik W5300 after adding expansion modules.
The following ioLogik E1200 models are supported for the I/O expansion: E1210 (16 DIs), E
1211 (16 DOs),
E1212 (8 DIs and 8 DIOs), E1214 (6 DIs and 6 Relays), E1240 (8 DIs), E1241 (4 AOs), E1242 (4 AIs, 4 DIs,
and 4 DIOs), E1260 (6 RTDs), and E1262 ( 8TCs). (And ALL T models)
The expansion support models are firmware version dependant. Versions earlier than V1.3-W5312,
V1.5-W5340, and V1.2-W5340-
HSDPA only support the following 5 models: E1210, E1211, E1212, E1214,
and E1240.
I/O Expansions Step-by-Step
Step 1: Configure the expansion module and Export its Configuration File.
Use the ioSearch utility, the ioLogik E1200’s configuration utility, or the web console to configure the target
E1200 modules and export the E1200’s configuration files. Note that all expansion modules should reside on
the same network segment as the ioLogik W5300.
Step 2: Import the configuration file to the ioLogik W5300.
Open ioAdmin and choose the “I/O Expansions” tab. Import these saved E1200 configuration files by pressing
the “Add” button.
Step 3: Connect the ioLogik W5300 and E1200.