ioLogik Cellular Micro RTU Controller Planning and Assistance
5-7
Expanding Input/Output Channels
Scenario: A monitoring system for a pumping station does not have enough I/O channels, and the user would
like to add more I/O channels to meet system requirements. In addition to the existing 4 AIs, 8 DIOs, and 2
Relay Outputs, they are using the ioLogik E1210 and E1211 to add an additional 16 DIs and 16 DOs.
Implementation:
Step 1: Connect to the ioLogik E1210 and E1211 and start the Web Consoles for these two products.
Step 2: Configure and export the configuration files of these two models. The file names will be ik1210.txt and
ik1211.txt.
Step 3: Use Ethernet cables to daisy-chain the W5340, E1210, and E1211, and connect to the host PC through
the E1211’s Ethernet port.
Step 4: Start ioAdmin with the selected W5340 and chooseI/O expansion.”
Step 5: Click the “Expansion Modules” row and then click the “ADD” button. ioAdmin will prompt you to import
the E1200 series configuration.
Step 6: In the open file window, choose the configuration file for the E1210 (e.g., ik1210.txt).
Step 7: You can find the E1210 in the “Expansion Modules” table. Repeat steps 5 and 6 to add the E1211.
Step 8: After adding the E1210 and E1211, reboot the W5340 to activate this function.