ioLogik MXIO DLL API Reference Direct I/O Command Sets
6-64
AO4K_SetSafeActions
This function code is used to set the safe actions of contiguous
A/O channels.
C/C++
Arguments
Return Value
int AO4K_SetSafeActions ( int hConnection,
BYTE bytSlot,
BYTE bytStartChannel,
BYTE bytCount,
WORD wAction[ ]);
hConnection: The handle for an I/O connection. bytSlot:
Slot number of the I/O module, from 1 to 32.
bytStartChannel: Specifies the starting channel.
bytCount: The number of channels to set.
wAction: An array that stores thesafe actions for the
contiguous A/O channels. wAction[0]
represents the value of the starting channel. The
values are:
0: Safe value
1: Hold last state
2: Low Limit
3: High Limit
Succeed MXIO_OK.
Fail Refer to Return Codes.
AO4K_GetSafeAction
This function code is used to get the safe action for a specific
analog output channel.
C/C++
Arguments
Return Value
int AO4K_GetSafeAction ( int hConnection,
BYTE bytSlot,
BYTE bytChannel,
WORD * wAction);
hConnection: The handle for an I/O connection. bytSlot:
Slot number of the I/O module, from 1 to 32.
bytChannel: The desired channel.
wAction: A pointer to the safe action of the desired A/O
channel. The values are:
0: Safe value
1: Hold last state
2: Low Limit
3: High Limit
Succeed MXIO_OK.