ioLogik E2260 User’s Manual Initial Setup
2-2
Hardware Installation
Connecting the Power
Connect the 12 to 48 VDC power line to the ioLogik E2260’s terminal block (TB1). If power is
properly supplied, the Power LED will glow a solid red color until the system is ready
ATTENTION
Disconnect the power before installing and wiring
Disconnect the power cord before installing and/or wiring your ioLogik E2260.
Do not exceed the maximum current for the wiring
Determine the maximum possible current for each power wire and common wire. Observe all
electrical codes dictating the maximum current allowable for each wire size.
If the current exceeds the maximum rating, the wiring could overheat, causing serious damage to
your equipment.
Grounding the ioLogik E2260
There are two grounding points on the ioLogik E2260: the wall mounting point and the DIN-rail
mounting plate. Note that both grounding points are actually connected to the same conducting
pathway.
Connecting to the Network
1. Connect the ioLogik E2260 to the host PC with an Ethernet cable. For initial setup of the
ioLogik E2260, it is recommended that the ioLogik E2260 be configured using a direct
connection to a host computer rather than remotely over the network.
2. Note the ioLogik’s default IP settings:
IP Address Netmask Gateway
192.168.127.254 255.255.255.0 None
Configure the host PC’s IP address to 192.168.127.xxx. (xxx: from 001 to 253) so the ioLogik
will be visible on the network. In Windows, you will need to do this through the Control Panel.
3. Use ioAdmin or the web console to detect the ioLogik E2260. Once the ioLogik E2260 has been
detected, modify the settings as needed for your network environment, then restart the ioLogik
E2260. For information on ioAdmin, please refer to Software Installation later in this chapter.
Setting the RS-485 Baudrate
The RS-485 port on the ioLogik E2260 is reserved for connecting to another RS-485 I/O server.
The RS-485 port can run Modbus/RTU or I/O command sets. The baudrate is set by a physical dial
on the back of the ioLogik E2260. The default settings are baudrate = 115200, parity check = N,
data bits = 8, and stop bit = 1.
Baudrate for RS-485
(parameters are N, 8, 1)
Dial setting and corresponding baudrate:
0:115200 1:57600 2:38400 3:19200
4:9600 5:4800 6:2400 7:1200
Remember to restart the ioLogik E2260 after making any changes to the RS-485 baudrate.