ioLogik E1500 Series Users Manual Second Edition, August 2012 www.moxa.com/product © 2012 Moxa Inc. All rights reserved.
ioLogik E1500 Series Introduction to the ioLogik E1500 1-6 Hardware Reference Panel Guide NOTE The reset button restarts the server and resets all
ioLogik E1500 Series Introduction to the ioLogik E1500 1-7 I/O Circuit Diagram Isolation DI (DI channels) DI Circuit (DIO channels) DO Circuit (DI
2 2. Initial Setup This chapter describes how to install the ioLogik E1500. The following topics are covered in this chapter: Hardware Installati
ioLogik E1500 Series Initial Setup 2-2 Hardware Installation Connecting the Power Connect the 12 to 48 VDC power line to the terminal block on the t
ioLogik E1500 Series Initial Setup 2-3 I/O Wiring Diagrams DI dry contact mode DI wet contact mode (Ch-Ch isolation) NOTE Pure DI is differential
ioLogik E1500 Series Initial Setup 2-4 DI wet contact PNP/NPN mode (No CH-CH isolation) DIO_DI wet contact mode (no CH-CH isolation) NOTE DIO is s
ioLogik E1500 Series Initial Setup 2-5 DIO_DO sink mode Software Installation ioSearch is a search utility that helps the user locate ioLogik E1500
3 3. Using the Web Console The ioLogik E1500’s main configuration and management utility is the built-in web console, which can be used to configure
ioLogik E1500 Series Using the Web Console 3-2 Introduction to the Web Console The ioLogik E1500 web console is a browser-based configuration utilit
ioLogik E1500 Series Using the Web Console 3-3 Overview The Overview page contains basic information about the ioLogik E1500, including the model na
ioLogik E1500 Series Users Manual The software described in this manual is furnished under a license agreement and may be used only in accordance with
ioLogik E1500 Series Using the Web Console 3-4 The Communication Watchdog activates Safe Mode after a specified amount of time has passed following
ioLogik E1500 Series Using the Web Console 3-5 Default Address On this settings page, you can view the default Modbus address for all I/O devices. T
ioLogik E1500 Series Using the Web Console 3-6 1. Check the Enable Active OPC checkbox and then specify the IP address where the Active OPC Server
ioLogik E1500 Series Using the Web Console 3-7 I/O Settings DI Channels The status of each DI (digital input) channel appears on the I/O Setting: DI
ioLogik E1500 Series Using the Web Console 3-8 By selecting the Save Status on Power Failure field, the ioLogik E1500 will automatically save the co
ioLogik E1500 Series Using the Web Console 3-9 You can also configure each channel’s digital input mode and parameters by clicking on the channel. D
ioLogik E1500 Series Using the Web Console 3-10 DO Channels can operate in DO mode and are either on or off. In Pulse Output mode, you can specify
ioLogik E1500 Series Using the Web Console 3-11 The Digital Output’s Alias Name and the logic definition can also be configured on this page. You ca
ioLogik E1500 Series Using the Web Console 3-12 Refer to the following table for additional configuration examples. Allowed Hosts IP address/Netmas
ioLogik E1500 Series Using the Web Console 3-13 Export System Configuration Settings On the Export System Config page, you can save the ioLogik’s co
Table of Contents 1. Introduction to the ioLogik E1500 ...
ioLogik E1500 Series Using the Web Console 3-14 Save/Restart If you change the configuration, don’t forget to reboot the system.
4 4. Using ioSearch This chapter describes ioSearch, which is used to search for and locate ioLogik E1500 units. The following topics are covered in
ioLogik E1500 Series Using ioSearch 4-2 Introduction to ioSearch ioSearch is for locating or searching for an ioLogik E1500 on the physical network.
ioLogik E1500 Series Using ioSearch 4-3 Main Items System Several operations are possible from the System menu. Auto Scan Active Ethernet I/O Server
ioLogik E1500 Series Using ioSearch 4-4 Sort The Sort menu allows the server list in the navigation panel to be sorted by ioLogik connection and ser
ioLogik E1500 Series Using ioSearch 4-5 Locate The locate function helps users find a dedicated ioLogik on the network. When this function is trigge
ioLogik E1500 Series Using ioSearch 4-6 Import Select this command to reload a configuration that was exported to a text file. Importing one confi
ioLogik E1500 Series Using ioSearch 4-7 Change IP Address The Change IP Address function can be used to directly modify the IP Address, especially f
ioLogik E1500 Series Using ioSearch 4-8 After the Advance button is clicked, a window will pop up to allow users to use ioSearch to set the IP addre
ioLogik E1500 Series Using ioSearch 4-9 Mass Deployment (Import) Users can import E1500 series module information via ioSearch. Select this command
5. Active OPC Server Utility ... 5-1
5 5. Active OPC Server Utility Active OPC Server is a software package provided by Moxa that operates as an OPC driver for an HMI or SCADA system. I
ioLogik E1500 Series Active OPC Server Utility 5-2 Active OPC Server Moxa Active OPC Server is a software package operated as an OPC driver of an HM
ioLogik E1500 Series Active OPC Server Utility 5-3 OPC Client/Server creates a common interface to connect to different devices Active OPC Server—F
ioLogik E1500 Series Active OPC Server Utility 5-4 The “push” technology also includes the update for the tags. When the I/O status changes, the ioL
ioLogik E1500 Series Active OPC Server Utility 5-5 Features of Active OPC Server One Simple Click Creates Active Tags Moxa’s RTUs, remote I/O device
ioLogik E1500 Series Active OPC Server Utility 5-6 Active OPC Server Overview Installing Active OPC Server Active OPC Server can be installed from t
ioLogik E1500 Series Active OPC Server Utility 5-7 The file will have an .mdb or .xls extension, and can be opened using Microsoft Office Access or
ioLogik E1500 Series Active OPC Server Utility 5-8 Auto-save Updated Configuration: Once you activate auto-save, the Active OPC will automatically s
A A. Modbus/TCP Default Address Mappings The following topics are covered in this appendix: E1510 User Defined Modbus E1512 User-Defined Modbu
ioLogik E1500 Series Modbus/TCP Default Address Mappings A-2 NOTE The Modbus/TCP ID of the ioLogik E1500 is set to “1” by default. E1510 User Defi
1 1. Introduction to the ioLogik E1500 The ioLogik E1500 Ethernet I/O product is housed in a rugged aluminum case, and is compliant with the EN 5012
ioLogik E1500 Series Modbus/TCP Default Address Mappings A-3 Reference Address Data Type Description 00277 0x0114 1 bit CH4 DI Clear Count V
ioLogik E1500 Series Modbus/TCP Default Address Mappings A-4 3xxxx Read only Registers (Support function 4) Dynamic Modbus 3xxxx Read Registers (S
ioLogik E1500 Series Modbus/TCP Default Address Mappings A-5 Reference Address Data Type Description DI Channel 40257 0x0100 1 bit CH0 DI C
ioLogik E1500 Series Modbus/TCP Default Address Mappings A-6 Read Always return:0 Write: 1 : Clear counter value 0 : Return illegal data val
ioLogik E1500 Series Modbus/TCP Default Address Mappings A-7 Reference Address Data Type Description 00262 0x0105 1 bit CH5 DI Counter Operate
ioLogik E1500 Series Modbus/TCP Default Address Mappings A-8 3xxxx Read only Registers (Support function 4) Dynamic Modbus 3xxxx Read Registers (Su
ioLogik E1500 Series Modbus/TCP Default Address Mappings A-9 Bit3 = Ch3 DO Value (0=OFF, 1=ON) Reference Address Data Type Description D
B B. Network Port Numbers ioLogik E1500 Network Port Usage Port Type Usage 80 TCP Web console service 502 TCP Modbus/TCP communication 68 UDP
C C. Factory Defaults ioLogik E1500 series products are configured with the following factory defaults: Default IP address 192.168.127.254 Default
D D. Pinouts Pin assignment of Terminal Blocks ioLogik E1510 (Bottom) (TOP) 1 N.C. 1 N.C. 2 N.C. 2 N.C. 3 +12 (Out) 3 +12 (Out
ioLogik E1500 Series Introduction to the ioLogik E1500 1-2 Quick Start Guide Overview 1. Product Features 2. Product Model Information Getting St
E E. FCC Interference Statement Federal Communication Commission Warning! This equipment has been tested and found to comply with the limits for a C
F F. European Community (CE) This is a Class A product. In a domestic environment, this product may cause radio interference in which case the user
ioLogik E1500 Series Introduction to the ioLogik E1500 1-3 Product Features • Compliant with EN 50121-3-2, EN 50121-4 and essential sections of EN
ioLogik E1500 Series Introduction to the ioLogik E1500 1-4 Operating Temperature: -40 to 85°C (-40 to 185°F) Storage Temperature: -40 to 85°C (-40 t
ioLogik E1500 Series Introduction to the ioLogik E1500 1-5 Wet Contact (DI to GND): • On: 0 to 3 VDC • Off: 10 to 30 VDC Common Type: 2 points per C