Moxa MGATE MB3180 Manual de usuario Pagina 15

  • Descarga
  • Añadir a mis manuales
  • Imprimir
  • Pagina
    / 88
  • Tabla de contenidos
  • MARCADORES
  • Valorado. / 5. Basado en revisión del cliente
Vista de pagina 14
MGate MB3000 User’s Manual Hardware: MB3180
3-4
Jumpers
To set the pull high/low resistors to 150 KΩ, leave jumpers JP3 and JP4 open (not shorted). This
is the default setting.
To set the pull high/low resistors to 1 KΩ, short jumpers JP3 and JP4 with jumper caps.
ATTENTION
Do not use the 1 Kpull high/low setting on the MGate MB3000 when using the RS-232 interface.
Doing so will degrade the RS-232 signals and reduce the effective communication distance.
Vista de pagina 14
1 2 ... 10 11 12 13 14 15 16 17 18 19 20 ... 87 88

Comentarios a estos manuales

Sin comentarios