MGate EIP3000 Series Users Manual Hardware: EIP3170, EIP3170I
Jumpers
SW 1
The DIP switches are located beneath the DIP switch panel on the side of the unit.
To add a 120 termination resistor, set switch 3 to ON; set switch 3 to OFF (the default setting) to
disable the termination resistor.
To set the pull high/low resistors to 150 K, set switches 1 and 2 to OFF. This is the default
setting.
To set the pull high/low resistors to 1 K, set switches 1 and 2 to ON.
Switch 4 on the port’s assigned DIP switch is reserved.
ATTENTION
Do not use the 1 K pull high/low setting on the MGate EIP3000 when using the RS-232 interface.
Doing so will degrade the RS-232 signals and reduce the effective communication distance.
3-4